Rated voltage: 40.5KV
Rated current: 1250、1600、2000、2500A
Propose: Outdoor load switching and line control、 rapid fault isolation and interruption、 automatic reclosing function、distribution network automation and intelligent operation and maintenance
Temperature: -40°C~+40°C、Alititude<1000m
Standards: IEC 62271-111、IEC 62271-1
ZW7-40.5kV Series - 华通大图
ZW7-40.5kV Series - 华通大图
Application & Technical Parameters
Environmental Conditions

♦ Ambient temperature: -40°C~+40°C;

♦ Altitude: <1000m;

♦ Maximum wind speed is 10km/h, minimum wind speed for the rated level (132/230kv) is 3.2km/h;

♦ Earthquake intensity: <8 level;

♦ Minimum nominal creepage distance: 31mm/kV;

♦ Air pollution degree: Class IV.


Main Technical Parameters

No

Item

Unit

Value

1

Rated voltage

kV

40.5

e

Ratedinsulationlevel

1 min power frequencyDry test (fracture, inter-phase, to earth)Wet test (to earth, external insulation)

kV

95
     85

Lightning impulse withstand voltage(peak)

185

3

Rated current

A

1250, 1600, 2000,
     2500

4

Rated short circuit breaking current

kA

20, 25, 31.5

5

Rated short circuit making current (peak)

kA

50, 63, 80

6

Rated peak withstand current

kA

50, 63, 80

7

Rated short time withstand current

kA

20, 25, 31.5

8

Rated operating sequence

 

O-0.3S-CO-180S-CO

9

Rated short circuit breaking current breaking number

times

20

10

Rated short circuit duration

s

4

11

Breaking time

s

≤0.09

12

Mechanical life

times

10000

13

Newly manufactured vacuum interrupter

Ps

≤1.33×10-3

Vacuum interrupter during 20-year storage time

<6.6×10-2

14

Circuit breaker net weight

kg

800

15

Clearance between open contacts

mm

22±2

16

Contact travel

mm

4±1

17

Average opening speed

m/s

1.4-1.7

18

Average closing speed

m/s

0.4-0.7

19

Contact closing bounce time

ms

≤3

20

Inter-phase opening and closing synchronism

ms

≤2

21

Closing time

ms

50≤t≤200

22

Opening time

ms

30≤t≤60

23

Each phase main circuit DC resistance (not includeCT internal resistance)

μΩ

≤100

24

Dynamic and fixed contact cumulative thickness allowed to wear

mm

3

25

Rated contact pressure

N

2500±200

General Structure Drawing and Installation Size

♦ Side-mechanism type

华通图片.png

♦ Mid-mechanism type

华通图片2.png

Spring operating mechanism

main data of operating mechanism of vacuum circuit breaker


Equipped with operating mechanism

Motor model power

Closing coil data

Opening coil data

Voltage

Resistance value

electric current

Voltage

Resistance value

electric current

V

Q

A

V

Q

A

Ct19bw projectile
     Spring operating mechanism

68ZY-CJ32-A
     DC220V 200W

-220

190

1.2

-220

135

1.69

-110

73

1. 3

-110

48

2. 3


The vacuum circuit breaker is equipped with lzzbj4-35 current transformer

Serial number:

group

purpose

capacity

level

1

1K

Measurement or measurement

15VA

0. 2 0. 2S

2

2K

Monitoring or measurement

25VA

0. 5

3

3K

Relay insurance

50VA

10P10

4

4K

Relay insurance

50VA

10P10

Ordinal date

Rated primary current
     (A)

Rated secondary current (a)

4S thermal stable power
     Stream (valid value)

Dynamic stable current (peak value)

1

50—200

5A

60Iin

150Iin

2

300—400

21kA

52.5kA

3

600—800

43kA

107. 5kA

4

1000—1250

63kA

157. 5kA

5

1500-1600

80kA

200kA

Note: Lin is the primary rated current

Structure of vacuum circuit breaker

华通图片.png

Secondary control diagram

华通图片.png

Installation diagram

华通图片.png